Navien · Combi boiler
E003 Ignition failure
What the control is telling you
The burner did not light (no flame proven) during the ignition attempts. NFC-H manual lists the reset type as: Manual reset.
Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)
Likely causes
- Main gas supply valve closed or gas supply interrupted
- Inlet gas pressure out of range
- Wrong gas type / orifice for the gas supplied
- Dirty or badly positioned ignition/flame detector electrode, poor ignition ground
Test and repair steps
- Make sure the main gas supply valve is open (the manual's listed remedy).
- Measure inlet gas pressure at full fire NG 3.5-10.5 in WC; LP 8.0-13.5 in WC (NCB-H) or 8.0-13.0 in WC (NFC-H).
- Confirm DIP SW2 #1 matches the gas supplied (OFF = natural gas, ON = propane) and the correct orifice is installed.
- Remove and clean the ignition/flame detector electrode; replace it if it cannot be cleaned, and check its gasket.
- Check the ignition ground wire is secure and has continuity to the casing.
- Check Service Status Info for repeated 2nd-10th ignition attempts to judge how often lighting is marginal.
- Reset from the front panel by pressing the Back button, then confirm the code clears.
- Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.
Settings for these units
Minimum installation clearances (indoor) · Navien NCB-H
| Side | Minimum |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
Indoor wall-hung only; ambient must stay above 32°F (0°C).
Do not install on carpet; leave room for service.
Water quality limits (DHW and system fill) · Navien NCB-H
| Contaminant | Max allowed |
|---|---|
| Total hardness | 200 mg/l (12 grains/gallon) |
| Aluminum | 0.05 to 0.2 mg/l |
| Chloride | 250 mg/l |
| Copper | 1.0 mg/l |
| Iron | 0.3 mg/l |
| Manganese | 0.05 mg/l |
| pH | 6.5 to 8.5 |
| Sulfate | 250 mg/l (DHW table); 205 mg/l (fill table) |
| Total dissolved solids | 500 mg/l |
| Zinc | 5 mg/l |
| Chlorine (fill water) | 4 mg/l |
Scale damage from poor water is not covered by warranty.
Manual shows sulfate 250 mg/l on p.23 and 205 mg/l on p.29 - check local guidance.
- Minimum installation clearances (indoor) · Navien NFC-H
- Water quality limits (DHW and system fill) · Navien NFC-H
Models that show this code
7 models in Navien NCB-H, Navien NFC-H
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.