Navien · Boiler

E030 Exhaust overheat

High severity Navien NHB-HNavien NFB-H

What the control is telling you

Flue gas temperature exceeded the limit. Manual action: check flow and clean system filters.

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • Low water flow through the heat exchanger
  • Dirty system filters
  • Return water too hot for the PVC exhaust limit
  • Exhaust thermistor fault

Test and repair steps

  1. Check flow through the boiler and clean the system return filter (see flow checks under E001).
  2. Read Exhaust Temp in Status Info while firing.
  3. Note with DIP SW2 #8 OFF the control limits exhaust to about 149°F (65°C) for PVC venting. Only set #8 ON if the exhaust is CPVC, approved PP or stainless steel.
  4. Check the return temperature setting/heat load; return water above 140°F (60°C) needs high-temperature vent material and SW2 #8 ON.
  5. If the reading looks wrong, check the exhaust thermistor connector (see E047).

Settings for these units

Installation clearances (indoor) · Navien NHB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.

Common vent installs: 36 in above the top and 24 in in front are recommended for service.

Installation clearances (indoor) · Navien NFB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Do not install on carpet; indoors only.

Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.

Models that show this code

6 models in Navien NHB-H, Navien NFB-H

NFB-175HNFB-200HNHB-055HNHB-080HNHB-110HNHB-150H

Other codes on the same units

  • E003 Ignition failure
  • E004 False flame detected
  • E012 Flame loss
  • E016 Heat exchanger overheat (check flow / system filters)
  • E031 Burner overheat
  • E046 Heat exchanger thermistor fault
  • E047 Exhaust thermistor fault
  • E060 Dual venturi fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.