Navien · Boiler
E012 Flame loss
What the control is telling you
The flame went out during operation. Manual action: check gas, venting and the condensate trap.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Low or unstable gas pressure
- Blocked or over-length vent / intake
- Condensate trap empty, blocked or backing up
- Dirty flame rod
- Wrong orifice or combustion setting
Test and repair steps
- Check inlet gas pressure at maximum fire NG 3.5-10.5 in WC, LP 8.0-13.0 in WC.
- Inspect the exhaust and intake for blockage, snow, separated joints, and verify length/elbows are within limits (2 in: 65 ft, 3 in: 150 ft; 90° = 8 ft / 5 ft).
- Check the condensate line slopes down at least 1/4 in per ft, is not frozen, and the trap is filled with water.
- Clean the flame rod and check the Flame Loss count in Service Status Info.
- Check the air intake filter for lint/dust.
- Verify CO2 at low and high fire against the combustion table; at high fire never adjust the valve - check the orifice instead.
Settings for these units
Installation clearances (indoor) · Navien NHB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.
Common vent installs: 36 in above the top and 24 in in front are recommended for service.
Installation clearances (indoor) · Navien NFB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Do not install on carpet; indoors only.
Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.
Models that show this code
6 models in Navien NHB-H, Navien NFB-H
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.