EC50 outdoor temperature sensor fault
What the control is telling you
The outdoor board reads the outdoor temperature sensor as open or shorted. Manual gives the meaning only; steps are standard sensor checks.
Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)
Likely causes
- Sensor connector loose or unplugged on outdoor board
- Damaged sensor wire
- Failed sensor
- Outdoor main board input fault
Test and repair steps
- Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
- Check the indoor unit display code first - the manual says indoor codes often point to the outdoor problem; see the service manual for detailed tests.
- Find the outdoor temperature sensor plug on the outdoor main board and reseat it.
- Inspect the sensor lead for cuts, chafing or crushed sections.
- Unplug the sensor and check it for open or short circuit with an ohmmeter (compare to the service manual resistance chart).
- Replace the sensor if open/shorted; if the sensor checks good, suspect the outdoor main board.
Settings for these units
Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)
| Side | Minimum |
|---|---|
| A - top | 24 in. (610 mm) |
| B - right side (service side) | 24 in. (610 mm) |
| C - front (air outlet) | 24 in. (610 mm) |
| D - left side | 4 in. (101 mm) |
| E - rear (air inlet) | 4 in. (101 mm) |
| Above max snow depth | 2 in. (50 mm) |
Side letters taken from Fig. 8 drawing.
Units facing each other: 59 in. (150 cm) or more; do not blow into another unit's inlet.
Models that show this code
12 models in Midea DLCURA ducted single-zone inverter heat pump (outdoor)
Other codes on the same units
- EC5C High pressure sensor failure
- EC07 Outdoor DC fan motor fault / speed out of control
- EC51 Outdoor EEPROM error
- EC52 condenser coil temperature sensor fault
- EC53 outdoor ambient temperature sensor fault
- EC54 Discharge temperature sensor (TP) open/short
- EC57 refrigerant pipe temperature sensor fault
- EC71 Outdoor DC fan motor over-current
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.