Midea · Furnace
FL Low flame signal
What the control is telling you
The control is seeing a weak flame signal. The furnace may still run but is at risk of flame dropouts (E8).
Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A)
Likely causes
- Dirty or broken flame sensor
- Poor control board ground
- Manifold or inlet gas pressure out of range
- Blocked burner orifices
- Faulty gas valve or control board
Test and repair steps
- Warning: Gas appliance - leak check with soap solution only.
- Clean the flame sensor with steel wool or replace it if broken.
- Check the control board / green ground wire is properly grounded.
- Check inlet gas pressure natural gas 4.5-10.5 in. WC, propane 11.0-13.0 in. WC; correct the supply if out of range.
- Check manifold pressure 3.5 in. WC natural gas, 10 in. WC propane; adjust the gas valve, and replace it if it cannot be adjusted.
- Inspect burners for blocked or clogged orifices and clear them.
- If all checks are good and FL persists, replace the control board.
Models that show this code
6 models in Midea 96% AFUE A2L Gas Furnace (BGH96M)
Other codes on the same units
- E6 Limit/rollout switch open more than 5 minutes
- E7 System lockout - failed ignition
- E8 System lockout - too many flame dropouts
- LED2 green 1 flash Refrigerant leak sensor communication failure
- LED2 green 2 flashes Refrigerant concentration above alarm limit (leak)
- LED2 green 3 flashes Sensor connected but SW1-2 OFF (DIP reminder)
- LED2 green 4 flashes Refrigerant sensor expired or faulty
- Pr Incorrect polarity of L1/L2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Section 3.7 FL chart, Tables 1-2, Fig. 12, p.21. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.