Midea · Furnace
E7 System lockout - failed ignition
What the control is telling you
The furnace failed to prove flame on its ignition attempts and has locked out. Manual notes the control auto-resets after 1 hour. (Manual says lockout after three attempts in Section 2.2 but after two failed attempts in Appendix A2.)
Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A)
Likely causes
- Gas valve switched OFF or no gas supply
- Low inlet or manifold gas pressure
- Ignitor not glowing / cracked (out of 9-17 ohms)
- No 115 V to ignitor or no 24 V to gas valve from board
- Blocked burner orifices
- Dirty or broken flame sensor / poor ground
- Loose or wrong wiring
- Faulty control board or gas valve
Test and repair steps
- Warning: Gas appliance - check for gas leaks with soap solution only, never an open flame.
- Make sure the gas valve switch is in the ON position.
- Check for loose or wrong wiring at the ignitor, gas valve and flame sensor; correct per the wiring diagram.
- Check inlet gas pressure natural gas 4.5-10.5 in. WC, propane 11.0-13.0 in. WC. Correct the supply if out of range.
- Watch the ignitor during the 17 s preheat: it should glow red/orange. If not, check for 115 VAC between IG and IGN during preheat (no voltage = board problem) and measure the ignitor at 9-17 ohms (out of range = replace ignitor).
- If the ignitor glows but no flame, check for 18-31 VAC between M/HI and C at the gas valve; no signal = replace the control board.
- Check manifold pressure 3.5 in. WC natural gas, 10 in. WC propane. Adjust the valve; replace the gas valve if it cannot be adjusted. Check burner orifices for blockage.
- If flame lights then drops out confirm flame reaches the sensor, clean the sensor with steel wool or replace it, and confirm flame signal is 1-6 microamps.
- Check the green ground wire is properly connected; poor ground causes flame-sense failure.
- Reset the lockout (power off 1-20 s or remove thermostat call 1-20 s). If faults continue with all checks good, replace the control board.
Models that show this code
6 models in Midea 96% AFUE A2L Gas Furnace (BGH96M)
Other codes on the same units
- E3 High pressure switch stuck open
- E4 Pressure switch cycle lockout
- E5 Limit/rollout switch open less than 5 minutes
- E6 Limit/rollout switch open more than 5 minutes
- E8 System lockout - too many flame dropouts
- LED2 green 1 flash Refrigerant leak sensor communication failure
- LED2 green 2 flashes Refrigerant concentration above alarm limit (leak)
- LED2 green 3 flashes Sensor connected but SW1-2 OFF (DIP reminder)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Section 3.2 E7/E8 chart, Figs. 9-12, Tables 1-2; Section 2.2, p.6, 10-11. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.