LED off Amber status LED off - no power / blown 3 A fuse
What the control is telling you
The control shows nothing. Usually no 115 V or 24 V at the board, an open door switch, or the 3-amp 24 V fuse is blown.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Blower door switch open
- Breaker off / no 115 V at L1-L2
- Blown 3-amp automotive fuse (24 V short)
- Failed transformer
Test and repair steps
- Warning: Manually closing the door switch exposes live 115 V parts - use caution.
- Check the breaker is on and there is 115 V at L1 and L2 on the control.
- Make sure the blower door is on and the door switch is closed; confirm 115 V reaches the switch, replace switch if power goes in but not out.
- Check for 24 V at SEC-1 and SEC-2; if 115 V is present but no 24 V, replace the transformer.
- If the 3-amp fuse is open, replace it with a 3-amp fuse ONLY, then disconnect thermostat leads to find the short in the 24 V wiring.
Models that show this code
6 models in ICP (F/G)9MAE Modulating Furnace
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.