7 Limit circuit lockout
What the control is telling you
Limit or rollout switch open more than 3 minutes, or 10 limit trips in a row at maximum heat. Auto-resets after 3 hours. Troubleshoot as code 4.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Same causes as code 4 - airflow restriction, blower problem, overfiring, failed limit/rollout
Test and repair steps
- Warning: Find why the limit/rollout opened before resetting - repeated trips mean overheating.
- Follow code 4 checks filter, ducts, blower wheel, gas input, limit switch and gasket.
- Manually reset rollout switch if tripped.
Models that show this code
6 models in ICP (F/G)9MAE Modulating Furnace
Other codes on the same units
- 4+3 Low/medium pressure switch open while medium/high switch closed
- 5 Abnormal flame-proving signal
- 6 Ignition proving failure
- 6+1 Ignition lockout
- 8 Gas heating lockout
- 9 Medium/high pressure switch or PSR relay did not close or reopened
- 10 Line voltage polarity
- LED off Amber status LED off - no power / blown 3 A fuse
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.