ICP · Furnace

8 Gas heating lockout

Critical severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

Control does NOT auto-reset. Turn off power, wait 5 minutes, retry.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • Gas valve relay on control stuck closed
  • Miswire or short to the gas valve BLUE wire

Test and repair steps

  1. Warning: Gas valve may be powered when it should not - verify gas valve closes.
  2. Turn power off and wait 5 minutes before retrying.
  3. Check the BLUE gas valve wire for miswiring or a short.
  4. If the code repeats, replace the furnace control (stuck relay).

Models that show this code

6 models in ICP (F/G)9MAE Modulating Furnace

G9MAE0601714G9MAE0602120G9MAE0801714G9MAE0802120G9MAE1002122G9MAE1202422

Other codes on the same units

  • 5 Abnormal flame-proving signal
  • 6 Ignition proving failure
  • 6+1 Ignition lockout
  • 7 Limit circuit lockout
  • 9 Medium/high pressure switch or PSR relay did not close or reopened
  • 10 Line voltage polarity
  • LED off Amber status LED off - no power / blown 3 A fuse
  • LED steady ON Amber LED on solid - control lockout / wrong model plug

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.