Gree · Heat pump

LC Compressor failed to start

High severity Gree SapphireGree Livo GEN4Gree Vireo GEN3Gree Multi21+

What the control is telling you

The compressor did not start. Multi21+ shows it as Lc.

Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)

Likely causes

  • Compressor stopped less than 3 min (pressures not balanced)
  • Compressor wiring loose or wrong sequence
  • Overcharge
  • Compressor failed
  • Outdoor board fault

Test and repair steps

  1. Wait at least 3 min after a stop before restarting.
  2. Check compressor U/V/W wiring against the diagram.
  3. Check the charge and remove any overcharge.
  4. Replace AP1 if the compressor checks good; otherwise replace the compressor.

Models that show this code

14 models in Gree Sapphire, Gree Livo GEN4, Gree Vireo GEN3, Gree Multi21+

3VIR09HP115V1A3VIR09HP230V1A3VIR12HP115V1A3VIR12HP230V1A3VIR18HP230V1A3VIR24HP230V1A4LIV30HP230V1AH4LIV36HP230V1AHMULTI18HP230V1COMULTI24HP230V1COSAP09HP230V1AHSAP12HP230V1AHSAP18HP230V1AHSAP24HP230V1AH

Other codes on the same units

  • Fo Refrigerant recovery (pump-down) mode
  • HC PFC protection
  • JF WiFi module fault
  • LP Indoor and outdoor units do not match
  • Ld Compressor phase loss
  • PH DC bus voltage too high
  • PL DC bus voltage too low
  • PU DC bus capacitor charging fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.