Goodman · Furnace
EEn Igniter open
What the control is telling you
The control sees an open igniter circuit (igniter burned out or disconnected).
Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92
Likely causes
- Igniter element open/cracked
- Igniter plug or wiring loose or broken
Test and repair steps
- Check the igniter plug and wiring back to the control.
- Power off, let the igniter cool and measure resistance: 37-68 ohms (silicon nitride), 30-300 ohms (80% carbide mini igniter). Open = replace.
- Handle the new igniter by its base only - touching the element or rough handling shortens its life.
- During warm-up the silicon nitride igniter should draw 0.37 to 0.68 A at 120 V (two-stage manuals).
Settings for these units
Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
80 models in Goodman/Amana GM9S96/AM9S96, Goodman/Amana GM9S80/AM9S80, Goodman/Amana GM9C96/AM9C96
Other codes on the same units
- EE9 High-stage pressure switch did not close
- EEA Reversed line polarity or grounding error
- EEC Internal gas valve error - valve energized when it should not be
- EEE Internal control fault (IRQ loss)
- EEH Twinning error
- EEJ Inducer relay error
- EEL Igniter relay / igniter circuit fault
- EEb External gas valve error - valve not energized when it should be
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.