Goodman · Furnace

EEH Twinning error

Low severity Goodman/Amana GM9S96/AM9S96Goodman/Amana GM9S80/AM9S80Goodman/Amana GM9C96/AM9C96

What the control is telling you

The twinning feature (two furnaces linked through the TWIN terminal) is not working.

Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92

Likely causes

  • Twin wiring loose or wrong
  • Furnaces not the same model or set differently
  • Furnaces powered from opposite panel legs
  • Control board fault

Test and repair steps

  1. Check the TWIN terminal wiring between the two furnaces and the thermostat wiring per the twinning diagram.
  2. Both furnaces must be the same model with the same staging and speed tap settings.
  3. Each furnace needs its own 115 VAC supply, with L1 on the same panel leg: L1 to L1 between the furnaces must read 0 V.
  4. If the wiring and settings are correct, replace the integrated control board.

Settings for these units

Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat (single stage)gH
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat (single stage)gH
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Models that show this code

80 models in Goodman/Amana GM9S96/AM9S96, Goodman/Amana GM9S80/AM9S80, Goodman/Amana GM9C96/AM9C96

AC9C96AC9S800403ANAC9S800603ANAC9S800804BNAC9S800805CNAC9S801005CNAC9S960403BNAC9S960603BNAC9S960804CNAC9S961005CNAC9S961205CNAC9S961205DNAM9C96AM9C960303ANAM9S800403ANAM9S800603ANAM9S800603BNAM9S800604BNAM9S800803BNAM9S800804BNAM9S800804CNAM9S800805CNAM9S801005CNAM9S801205DNAM9S920403ANAM9S920603BNAM9S920803BNAM9S920804CNAM9S920805CNAM9S921004CNAM9S921005CNAM9S921205DNAM9S960403ANAM9S960603BNAM9S960803BNAM9S960804CNAM9S960805CNAM9S961004CNAM9S961005CNAM9S961205DNGC9C96GC9S800403ANGC9S800603ANGC9S800804BNGC9S800805CNGC9S801005CNGC9S960403BNGC9S960603BNGC9S960804CNGC9S961005CNGC9S961205CNGC9S961205DNGM9C96GM9C960303ANGM9S800403ANGM9S800603ANGM9S800603BNGM9S800604BNGM9S800803BNGM9S800804BN

Other codes on the same units

  • EE9 High-stage pressure switch did not close
  • EEA Reversed line polarity or grounding error
  • EEC Internal gas valve error - valve energized when it should not be
  • EEE Internal control fault (IRQ loss)
  • EEJ Inducer relay error
  • EEL Igniter relay / igniter circuit fault
  • EEb External gas valve error - valve not energized when it should be
  • EEn Igniter open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.