Goodman · Furnace

EE8 High-stage pressure switch closed at start of heating cycle

Medium severity Goodman/Amana GM9C96/AM9C96

What the control is telling you

On a two-stage furnace the high-stage pressure switch circuit is already closed at the start of a heat call. The furnace runs on low stage only (inducer still operates). Flowcharts call this code E8.

Applies to: Goodman/Amana two-stage 96% furnaces GM9C96, GC9C96, AM9C96, AC9C96

Likely causes

  • High-stage pressure switch contacts stuck closed
  • Short in the pressure switch circuit wiring

Test and repair steps

  1. Power off, remove the wires from the high-stage pressure switch and ohm the contacts with the inducer off - they must be open.
  2. Replace the high-stage pressure switch if the contacts are closed with no vacuum.
  3. If the switch is good, find and repair the short in the switch wiring.
  4. Retest a high-fire call (W1+W2) and confirm the furnace stages up.

Settings for these units

Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat, low stagegH1
Gas heat, high stagegH2
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96

ConfigurationSize codeMinimum filter
Upflow*0403A*1 - 16 x 25 side or 1 - 14 x 24 bottom return
Upflow*0603A*1 - 16 x 25 side or 14 x 24 bottom return
Upflow*0603B*1 - 16 x 25 side or bottom return
Upflow*0803B*1 - 16 x 25 side or bottom return
Upflow*0804B*1 - 16 x 25 side or bottom return
Upflow*0804C*1 - 16 x 25 side or bottom return
Upflow*0805C*1 - 16 x 25 side or bottom return (see note 1)
Upflow*0805D*2 - 16 x 25 side or 1 - 20 x 25 bottom return (see note 1)
Upflow*1004C*2 - 16 x 25 side or 1 - 20 x 25 bottom return
Upflow*1005C*2 - 16 x 25 side or 1 - 20 x 25 bottom return
Upflow*1205D*2 - 16 x 25 side or 1 - 24 x 24 bottom return
Downflow*0403A*2 - 10 x 20 or 1 - 14 x 25 top return

Note 1: with a cooling unit over 4 tons use 2 - 16 x 25 filters on two side returns or a 20 x 25 on the bottom return.

Upflow at 1800 CFM or more: use two side returns or one side plus bottom.

Models that show this code

6 models in Goodman/Amana GM9C96/AM9C96

AC9C96AM9C96AM9C960303ANGC9C96GM9C96GM9C960303AN

Other codes on the same units

  • EE3 High (primary) limit open
  • EE4 Flame sensed with no call for heat
  • EE5 Open fuse (short in low voltage wiring)
  • EE6 Low flame signal
  • EE9 High-stage pressure switch did not close
  • EEA Reversed line polarity or grounding error
  • EEC Internal gas valve error - valve energized when it should not be
  • EEE Internal control fault (IRQ loss)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6612020r1 (GM9C96/GC9C96/AM9C96/AC9C96 service), 2 Stage Troubleshooting Codes, p.36; Error Code E1, E2 flowchart p.40. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.