Goodman · Furnace

EE4 Flame sensed with no call for heat

Critical severity Goodman/Amana GM9S96/AM9S96Goodman/Amana GM9S80/AM9S80Goodman/Amana GM9C96/AM9C96

What the control is telling you

The control sees a flame signal when the gas valve should be closed. The inducer and circulator blower run continuously and the furnace will not operate.

Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92

Likely causes

  • Short to ground in the flame sensor or its wiring
  • Lingering burner flame
  • Gas valve closing slowly or leaking through

Test and repair steps

  1. Warning: if a flame is actually present with no call for heat, shut the manual gas valve immediately.
  2. Look into the burner compartment if there is no flame, the signal is false - check the flame sensor wire and insulator for a short to ground and repair it.
  3. If a flame lingers after the call ends, the gas valve is not closing properly - replace the gas valve.
  4. After repair, cycle power and confirm the inducer and blower stop at the end of the post-purge and fan-off delay.

Settings for these units

Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat (single stage)gH
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat (single stage)gH
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Models that show this code

80 models in Goodman/Amana GM9S96/AM9S96, Goodman/Amana GM9S80/AM9S80, Goodman/Amana GM9C96/AM9C96

AC9C96AC9S800403ANAC9S800603ANAC9S800804BNAC9S800805CNAC9S801005CNAC9S960403BNAC9S960603BNAC9S960804CNAC9S961005CNAC9S961205CNAC9S961205DNAM9C96AM9C960303ANAM9S800403ANAM9S800603ANAM9S800603BNAM9S800604BNAM9S800803BNAM9S800804BNAM9S800804CNAM9S800805CNAM9S801005CNAM9S801205DNAM9S920403ANAM9S920603BNAM9S920803BNAM9S920804CNAM9S920805CNAM9S921004CNAM9S921005CNAM9S921205DNAM9S960403ANAM9S960603BNAM9S960803BNAM9S960804CNAM9S960805CNAM9S961004CNAM9S961005CNAM9S961205DNGC9C96GC9S800403ANGC9S800603ANGC9S800804BNGC9S800805CNGC9S801005CNGC9S960403BNGC9S960603BNGC9S960804CNGC9S961005CNGC9S961205CNGC9S961205DNGM9C96GM9C960303ANGM9S800403ANGM9S800603ANGM9S800603BNGM9S800604BNGM9S800803BNGM9S800804BN

Other codes on the same units

  • EE0 Lockout - too many ignition retries (3)
  • EE1 Pressure switch closed at start of heating cycle
  • EE2 Pressure switch did not close (inducer runs, no ignition)
  • EE3 High (primary) limit open
  • EE5 Open fuse (short in low voltage wiring)
  • EE6 Low flame signal
  • EE8 High-stage pressure switch closed at start of heating cycle
  • EE9 High-stage pressure switch did not close

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.