Goodman · Air handler
RDS 4 flashes R32 sensor internal fault
What the control is telling you
Red LED flashes 4 times, then off 5 s: communication with the sensor is fine but the sensor reports an internal fault.
Applies to: R-32 air handlers with refrigerant detection system (A2L PCB + R32 sensor): AMST, AWSF/AWST, ACSF
Likely causes
- Failed R32 sensor
Test and repair steps
- Unplug and reconnect the R32 sensor, then power cycle.
- If normal or delay mode returns, no further action.
- If 4 flashes remain, replace the sensor (use only the manufacturer-specified sensor).
Models that show this code
4 models in Goodman/Amana R-32 AMST/AWSF/ACSF air handlers
Other codes on the same units
- RDS 2 flashes Control board internal fault (leak detection board)
- RDS 3 flashes R32 sensor communication fault
- RDS fast flash R-32 leak alarm (or system verification test)
- RDS steady on Delay mode after leak alarm or fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), A2L PCB Fault Code and Recommended Action table p.25-26. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.