RDS 3 flashes R32 sensor communication fault

High severity Goodman/Amana R-32 AMST/AWSF/ACSF air handlers

What the control is telling you

Red LED flashes 3 times, then off 5 s: the board cannot talk to the R32 sensor.

Applies to: R-32 air handlers with refrigerant detection system (A2L PCB + R32 sensor): AMST, AWSF/AWST, ACSF

Likely causes

  • Faulty sensor
  • Faulty sensor harness
  • Fault inside the board

Test and repair steps

  1. Unplug and reconnect the R32 sensor, then power cycle.
  2. If the board returns to normal or delay mode, no further action.
  3. If 3 flashes remain (with the connector properly seated), replace both the sensor and the board - the fault cannot be isolated further in the field.

Models that show this code

4 models in Goodman/Amana R-32 AMST/AWSF/ACSF air handlers

ACSF****13**AAAMST***U1300AAAWSF****13**AAAWST****13**AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), A2L PCB Fault Code and Recommended Action table p.25-26. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.