Goodman · Air handler

RDS 2 flashes Control board internal fault (leak detection board)

High severity Goodman/Amana R-32 AMST/AWSF/ACSF air handlers

What the control is telling you

Red LED flashes 2 times, then off 5 s: the A2L board has found a problem with the detection system.

Applies to: R-32 air handlers with refrigerant detection system (A2L PCB + R32 sensor): AMST, AWSF/AWST, ACSF

Likely causes

  • Internal fault on the A2L control board
  • Sensor or connection problem (to be ruled out)

Test and repair steps

  1. Unplug and reconnect the R32 sensor, then power cycle.
  2. If the board shows normal or delay mode, the issue is gone.
  3. If not, unplug the sensor and leave it unplugged, then power cycle.
  4. Still 2 flashes = replace the board. Changes to 3 flashes = replace the sensor.

Models that show this code

4 models in Goodman/Amana R-32 AMST/AWSF/ACSF air handlers

ACSF****13**AAAMST***U1300AAAWSF****13**AAAWST****13**AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), A2L PCB Fault Code and Recommended Action table p.25-26. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.