Daikin · Furnace

EEL Igniter relay / igniter circuit fault

High severity Daikin DR96TN/DD96TN

What the control is telling you

The control detected a problem in the igniter circuit: wiring, a shorted or improperly connected igniter, poor ground, or a failed igniter relay on the board.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Wiring problem between control and igniter
  • Shorted or improperly connected igniter
  • Poor unit ground
  • Igniter relay fault on the integrated control

Test and repair steps

  1. Check and correct the wiring and plug between the integrated control and the igniter.
  2. Ohm the igniter at room temperature (37-68 ohms silicon nitride; 30-300 ohms carbide mini igniter on 80% models); replace a shorted igniter.
  3. Verify the unit ground wire runs back to the panel and the ground connection is tight.
  4. During igniter warm-up, check for 115 VAC output at the control's igniter terminals; no output with a good igniter and wiring = replace the control board.

Settings for these units

Normal status displays (7-segment) · Daikin DR96TN/DD96TN

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat, low stagegH1
Gas heat, high stagegH2
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Models that show this code

13 models in Daikin DR96TN/DD96TN

DD96TN0403BNDD96TN0603BNDD96TN0803BNDD96TN1005CNDR96TN0303ANDR96TN0403ANDR96TN0603ANDR96TN0603BNDR96TN0803BNDR96TN0804CNDR96TN1004CNDR96TN1005CNDR96TN1205DN

Other codes on the same units

  • EEC Internal gas valve error - valve energized when it should not be
  • EEE Internal control fault (IRQ loss)
  • EEH Twinning error
  • EEJ Inducer relay error
  • EEb External gas valve error - valve not energized when it should be
  • EEn Igniter open
  • EbL Low circulator current - hard lockout
  • EbU Unexpected circulator current - hard lockout

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.