Bosch · Boiler
E9 Safety high limit or flue gas limiter tripped
What the control is telling you
A heat exchanger safety limit or the flue gas temperature limiter has opened. The same code is used when the pump has seized.
Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers
Likely causes
- Faulty limiter or wiring
- Low system pressure or trapped air
- Pump capacitor weak or pump seized
- Blown PCB fuse
- Clogged DHW side of the heat exchanger
Test and repair steps
- Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
- Check both the flue gas limiter and heat exchanger limiter and their leads.
- Check the system operating pressure and purge the appliance.
- Check the pump capacitor and replace the pump if bad.
- Check the PCB fuse (6.3 A per IEC) and replace if blown.
- Check the DHW side of the heat exchanger and replace if blocked.
Models that show this code
4 models in Bosch Greenstar
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.