Bosch · Boiler

d5 External supply temperature sensor fault (low-loss header)

Medium severity Bosch Greenstar

What the control is telling you

The external supply sensor was seen on the BUS and then connected to its terminal, but is now faulty.

Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers

Likely causes

  • Sensor or lead open/shorted
  • Two supply sensors connected

Test and repair steps

  1. Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
  2. Check the sensor and leads.
  3. Make sure only one such sensor is connected; remove the extra one.
  4. Restore factory defaults with 8.E if needed.

Models that show this code

4 models in Bosch Greenstar

ZBR21-3AZBR28-3AZBR35-3AZBR42-3A

Other codes on the same units

  • b2/b3/b4/b5/b6 Internal data error
  • b7 Burner control fault
  • C6 Fan not running
  • d3 High limit / temperature limiter circuit open
  • E2 Supply temperature sensor fault
  • E3 Additional supply temperature sensor fault
  • E9 Safety high limit or flue gas limiter tripped
  • F0 Internal fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.