Bosch · Boiler
d3 High limit / temperature limiter circuit open
What the control is telling you
The temperature limiter circuit is open or an external limit has tripped, locking the boiler out.
Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers
Likely causes
- Sensor or lead open or shorted
- Temperature guard TB1 tripped or jumper missing across 8-9 or PR-P0
- External limit, LWCO or pressure device tripped
- Air in the system or low water pressure
Test and repair steps
- Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
- Check the sensor and leads for breaks or shorts.
- If no outside guard device is used, make sure the link across 8-9 or PR-P0 is in place.
- Reset any external temperature limiter, LWCO or pressure device that is installed.
- Purge the boiler and check the water pressure (this fault can appear at first start-up if air remains).
Models that show this code
4 models in Bosch Greenstar
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.