Trane · Furnace
E4.0 Main high limit open
What the control is telling you
The main thermal limit opened because it sensed too much heat. Check both 1st and 2nd stage operation.
Applies to: Trane S8V2 only
Likely causes
- Dirty filter or blower wheel
- External static above nameplate, undersized ducts
- Return air above 85 F
- Manifold pressure too high
- Loose insulation or objects in the air stream
- Faulty limit
Test and repair steps
- Warning: Never leave a limit switch jumpered; jumpers are for brief testing only.
- On a 1st stage call, measure 24 VAC across the main limit: voltage means it is open.
- Check external static pressure against the nameplate and correct duct problems if high.
- Measure temperature rise and compare to the rating plate; check return air is not above 85 F.
- Confirm manifold pressure is in range; correct if over-firing.
- Look inside the cabinet for loose insulation or debris.
- If all checks pass but the limit sees a temperature above its setting, fix airflow; if it opens below its setting, replace it. Keep test probes within 1/4 in. of the limit disc.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
Models that show this code
12 models in Trane S8V2
Other codes on the same units
- E3.1 1st stage pressure switch (PS1) closed when it should be open
- E3.2 1st stage pressure switch (PS1) open when it should be closed
- E3.3 2nd stage pressure switch (PS2) closed when it should be open
- E3.4 2nd stage pressure switch (PS2) open when it should be closed
- E4.1 Reverse airflow limit open
- E4.2 Flame rollout switch open
- E05 Flame sensed when no flame should be present
- E6.1 120 V polarity reversed
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.