Trane · Furnace
E3.2 1st stage pressure switch (PS1) open when it should be closed
What the control is telling you
PS1 did not close after the inducer started (S8X2 reports it after 60 seconds and speeds the inducer up to try to close it). Wind gusts can cause occasional PS1 open errors.
Applies to: Trane S8V2 (80%, 2-stage, variable speed, Link) and S8B1 / S8X1 / S8X2 (80%, 1- and 2-stage)
Likely causes
- Blocked, undersized or too-long vent
- Hose cracked, plugged or full of water
- Weak or failed inducer
- Wiring fault
- Faulty switch (least likely)
Test and repair steps
- Confirm PS1 wiring and hose routing match the wiring diagram; in most cases the switch itself is fine.
- Cycle power and call for 1st stage heat; measure voltage across PS1 (orange to yellow): 24 V means open, 0 V means closed.
- Check the inducer runs; if not, measure about 120 VAC at the inducer motor leads - voltage present means a bad inducer, none means IFC or wiring.
- Measure the draft at the switch with a manometer and compare to the set point printed on the switch label (negative pressure, compare magnitude).
- Look for blocked or undersized vent, kinked or wet hose, then replace the switch only if draft is above the label value and it still reads open.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
- Return filter size by cabinet width · Trane S8B1, Trane S8X1, Trane S8X2
Models that show this code
37 models in Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2
Other codes on the same units
- E2.1 Ignition retries exceeded - flame never proven (1 hour lockout)
- E2.2 Flame recycles exceeded - flame lost after lighting (1 hour lockout)
- E2.3 1st stage gas valve not powered when it should be (10 times)
- E3.1 1st stage pressure switch (PS1) closed when it should be open
- E3.3 2nd stage pressure switch (PS2) closed when it should be open
- E3.4 2nd stage pressure switch (PS2) open when it should be closed
- E04 Open limit (main limit, rollout or reverse airflow)
- E4.0 Main high limit open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts); Trane 18-CE14D1-1A-EN (S8B1/S8X1/S8X2 installer's guide) - section Integrated Furnace Control Display Codes, Error Codes. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.