Navien · Tankless water heater
E788 Gas type mismatch: DIP switch vs panel setting
What the control is telling you
The gas type on front-panel DIP switch 1 does not match the gas type stored in the panel. Expected right after changing DIP switch 1 during a conversion.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
Likely causes
- DIP switch 1 changed (gas conversion)
- Panel gas setting not updated
Test and repair steps
- Confirm the gas supplied and the rating plate.
- Set DIP switch 1 OFF natural gas, ON propane (power off when changing).
- Power on; in the error screen press Back to open Gas Type Check in the Start-Up Wizard and select the gas type.
- On propane, accept the Gas Conversion Kit Required prompt. The error then clears and the unit fires.
- After any conversion, check CO2 or the low-fire offset pressure against the conversion tables.
Settings for these units
Installation clearances (indoor / outdoor) · Navien NPE-2
| Side | Indoor | Outdoor |
|---|---|---|
| Top | 9 in. (229 mm) | 36 in. (900 mm) |
| Back | 0.5 in. (13 mm) | 0.5 in. (13 mm) |
| Front | 4 in. (100 mm) | 24 in. (600 mm) |
| Sides | 3 in. (76 mm) | 3 in. (76 mm) |
| Bottom | 12 in. (300 mm) | 12 in. (300 mm) |
Vent clearance to combustibles is 0 in.
Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only.
Water quality limits and flushing schedule · Navien NPE-2
| Hardness | grains/gal (mg/L) | Treatment | Flush frequency |
|---|---|---|---|
| Soft | 0-4 (0-60) | None | None |
| Moderately hard | 4-7 (61-120) | None required | Once a year |
| Hard | 7-9 (121-160) | Softener or Navien PeakFlow recommended | Once a year |
| Very hard | 9-12 (161-200) | Softener or PeakFlow highly recommended | Residential once a year; commercial twice a year |
| Extremely hard | >12 (200) | Softener or PeakFlow required | - |
Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5.
Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler.
Models that show this code
7 models in Navien NPE-2
Other codes on the same units
- E615 Input and memory abnormal
- E736 Cascade communication abnormal
- E740 Outdoor temperature sensor abnormal (with air handler)
- E760 Flushing / service alarm
- E762 Vent pipe not properly inserted
- E773 Wrong gas type detected
- E782 Main / panel communication abnormal
- E785 Flow switch / sensor abnormal (with air handler)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.18; Navien NPE-A2/S2 Installation Manual, 8.1, p.112. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.