Navien · Tankless water heater

E740 Outdoor temperature sensor abnormal (with air handler)

Low severity Navien NPE-2

What the control is telling you

Outdoor reset is on but the outdoor sensor is missing or reads out of range.

Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2

Likely causes

  • Outdoor sensor not connected
  • Sensor or wiring fault

Test and repair steps

  1. Check the outdoor sensor wiring at the H2Air controller.
  2. If outdoor reset is not wanted, set H2Air DIP switch 1 ON (outdoor reset off). While the error is active the system runs as if outdoor reset were off.
  3. Check Status Information > 16. AHU Outdoor Temp.
  4. Fix given phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Installation clearances (indoor / outdoor) · Navien NPE-2

SideIndoorOutdoor
Top9 in. (229 mm)36 in. (900 mm)
Back0.5 in. (13 mm)0.5 in. (13 mm)
Front4 in. (100 mm)24 in. (600 mm)
Sides3 in. (76 mm)3 in. (76 mm)
Bottom12 in. (300 mm)12 in. (300 mm)

Vent clearance to combustibles is 0 in.

Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only.

Water quality limits and flushing schedule · Navien NPE-2

Hardnessgrains/gal (mg/L)TreatmentFlush frequency
Soft0-4 (0-60)NoneNone
Moderately hard4-7 (61-120)None requiredOnce a year
Hard7-9 (121-160)Softener or Navien PeakFlow recommendedOnce a year
Very hard9-12 (161-200)Softener or PeakFlow highly recommendedResidential once a year; commercial twice a year
Extremely hard>12 (200)Softener or PeakFlow required-

Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5.

Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler.

Models that show this code

7 models in Navien NPE-2

NPE-150S2NPE-180A2NPE-180S2NPE-210A2NPE-210S2NPE-240A2NPE-240S2

Other codes on the same units

  • E593 Front panel key abnormal
  • E594 EEPROM abnormal
  • E615 Input and memory abnormal
  • E736 Cascade communication abnormal
  • E760 Flushing / service alarm
  • E762 Vent pipe not properly inserted
  • E773 Wrong gas type detected
  • E782 Main / panel communication abnormal

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.18. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.