Navien · Tankless water heater

E003 Ignition failure

High severity Navien NPE-2

What the control is telling you

The burner did not light during the ignition attempt.

Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2

Likely causes

  • Manual gas valve closed or gas supply interrupted
  • Inlet gas pressure too low (undersized line, regulator, meter capacity)
  • Gas type DIP switch 1 does not match the gas supplied
  • Air in a new gas line

Test and repair steps

  1. Make sure the manual gas shut-off valve to the unit and the main supply are fully open (manual's first action).
  2. Measure inlet gas pressure at the pressure port with several high-flow fixtures open (max fire): 3.5-10.5 in. WC natural gas, 8.0-13 in. WC propane.
  3. Check the gas line 3/4 in. connection, no 1/2 in. corrugated connector, meter capacity covers all connected appliances; Navien recommends the heater be the first appliance off the meter.
  4. Confirm front-panel DIP switch 1 matches the gas (OFF = natural gas, ON = propane) and the rating plate.
  5. On a new install, purge air from the gas line and retry.
  6. Check Installer Menu > 1. Service Status Info for repeated 2nd/3rd/4th ignition counts.
  7. Reset once with the Back button on the front panel and note whether the code returns.
  8. Code back after a reset? Stay at the unit and phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Installation clearances (indoor / outdoor) · Navien NPE-2

SideIndoorOutdoor
Top9 in. (229 mm)36 in. (900 mm)
Back0.5 in. (13 mm)0.5 in. (13 mm)
Front4 in. (100 mm)24 in. (600 mm)
Sides3 in. (76 mm)3 in. (76 mm)
Bottom12 in. (300 mm)12 in. (300 mm)

Vent clearance to combustibles is 0 in.

Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only.

Water quality limits and flushing schedule · Navien NPE-2

Hardnessgrains/gal (mg/L)TreatmentFlush frequency
Soft0-4 (0-60)NoneNone
Moderately hard4-7 (61-120)None requiredOnce a year
Hard7-9 (121-160)Softener or Navien PeakFlow recommendedOnce a year
Very hard9-12 (161-200)Softener or PeakFlow highly recommendedResidential once a year; commercial twice a year
Extremely hard>12 (200)Softener or PeakFlow required-

Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5.

Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler.

Models that show this code

7 models in Navien NPE-2

NPE-150S2NPE-180A2NPE-180S2NPE-210A2NPE-210S2NPE-240A2NPE-240S2

Other codes on the same units

  • E004 False flame detection
  • E012 Flame loss
  • E016 Heat exchanger overheating
  • E030 Exhaust overheating
  • E031 Burner overheating
  • E046 Limit control abnormal
  • E047 Exhaust thermistor open or shorted
  • E060 Dual venturi abnormal

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.