Navien · Combi boiler

E762 Vent pipe not fully inserted (VID)

Critical severity Navien NCB-HNavien NFC-H

What the control is telling you

The Vent Installation Detector switch in the exhaust collar does not detect a fully inserted vent pipe; the boiler will not run. NFC-H manual lists the reset type as: Auto reset.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • Vent pipe not pushed fully 2-3/4 in (70 mm) into the collar
  • Wrong pipe size, deformed pipe, misaligned or moving pipe
  • Street elbow used at the collar

Test and repair steps

  1. Warning: carbon monoxide hazard - do not run the boiler with a loose vent connection.
  2. Mark the pipe 2-3/4 in (70 mm) from the end, cut square (90°) and deburr, lubricate with water (not grease) and push in with a twist until the mark disappears.
  3. Use the correct 2 in pipe at the collar; never start the run with a street elbow - use a straight length.
  4. Tighten the collar clamp (8 mm socket) and support the pipe so it cannot move vertically.
  5. Bubble-test the exhaust joints with the boiler running.
  6. Note the VID does not detect leaks or separation further along the vent; inspect the whole run.

Settings for these units

Minimum installation clearances (indoor) · Navien NCB-H

SideMinimum
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)

Indoor wall-hung only; ambient must stay above 32°F (0°C).

Do not install on carpet; leave room for service.

Water quality limits (DHW and system fill) · Navien NCB-H

ContaminantMax allowed
Total hardness200 mg/l (12 grains/gallon)
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Copper1.0 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
pH6.5 to 8.5
Sulfate250 mg/l (DHW table); 205 mg/l (fill table)
Total dissolved solids500 mg/l
Zinc5 mg/l
Chlorine (fill water)4 mg/l

Scale damage from poor water is not covered by warranty.

Manual shows sulfate 250 mg/l on p.23 and 205 mg/l on p.29 - check local guidance.

Models that show this code

7 models in Navien NCB-H, Navien NFC-H

NCB-190/060HNCB-190/080HNCB-240/110HNCB-240/130HNCB-250/150HNFC-250/175HNFC-250/200H

Other codes on the same units

  • E615 Memory fault (input and memory)
  • E736 Cascade communication fault
  • E740 Outdoor sensor not detected
  • E761 Pump aquastat (pre-heat aquastat) not detected
  • E773 Improper gas type detected
  • E777 Low water cutoff (LWCO) activated
  • E782 Front panel communication fault
  • E784 Zone controller communication fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.