Navien · Combi boiler

E740 Outdoor sensor not detected

Low severity Navien NCB-HNavien NFC-H

What the control is telling you

Outdoor reset is enabled but the outdoor temperature sensor is not read. NFC-H: appears only when the outdoor reset curve is enabled. The boiler then runs on the set space heating temperature. NFC-H manual lists the reset type as: Alarm.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • Outdoor sensor not installed
  • Open or loose sensor wiring
  • Outdoor reset enabled by mistake

Test and repair steps

  1. Make sure the outdoor reset curve is set up correctly (the manual's listed remedy).
  2. Check the outdoor sensor wiring at the terminal block; use 18 gauge thermostat wire with no splices, routed away from line voltage.
  3. Check Status Information > 13. Outdoor Temp.
  4. If no sensor is installed, set Space Htg Operation > 3. Outdoor Reset ON/OFF to Disable.

Settings for these units

Minimum installation clearances (indoor) · Navien NCB-H

SideMinimum
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)

Indoor wall-hung only; ambient must stay above 32°F (0°C).

Do not install on carpet; leave room for service.

Water quality limits (DHW and system fill) · Navien NCB-H

ContaminantMax allowed
Total hardness200 mg/l (12 grains/gallon)
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Copper1.0 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
pH6.5 to 8.5
Sulfate250 mg/l (DHW table); 205 mg/l (fill table)
Total dissolved solids500 mg/l
Zinc5 mg/l
Chlorine (fill water)4 mg/l

Scale damage from poor water is not covered by warranty.

Manual shows sulfate 250 mg/l on p.23 and 205 mg/l on p.29 - check local guidance.

Models that show this code

7 models in Navien NCB-H, Navien NFC-H

NCB-190/060HNCB-190/080HNCB-240/110HNCB-240/130HNCB-250/150HNFC-250/175HNFC-250/200H

Other codes on the same units

  • E517 DIP switch setting fault
  • E594 EEPROM fault
  • E615 Memory fault (input and memory)
  • E736 Cascade communication fault
  • E761 Pump aquastat (pre-heat aquastat) not detected
  • E762 Vent pipe not fully inserted (VID)
  • E773 Improper gas type detected
  • E777 Low water cutoff (LWCO) activated

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.