P9 Coil sensor TH5 open or shorted
What the control is telling you
The condenser/evaporator thermistor TH5 reads 90°C or more, or -40°C or less, and does not recover after 3 minutes. Checked in cool, dry and heat (not during defrost).
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Likely causes
- TH5 thermistor out of range
- Loose connector CN44 on the indoor control board
- Broken wire in the thermistor lead
- Refrigerant circuit problem driving the coil temperature to an extreme
- Faulty indoor control board
Test and repair steps
- Turn the unit off at the remote first, then switch off the breaker before opening the unit or unplugging connectors.
- Unplug TH5 at CN44 and measure it. Thermistor values (approx.): 0°C 15 kΩ, 10°C 9.6 kΩ, 20°C 6.3 kΩ, 25°C 5.2 kΩ, 30°C 4.3 kΩ, 40°C 3.0 kΩ. Open or short = bad sensor.
- Reseat CN44 and retry.
- In test mode, read the coil temperature on the remote. Extreme readings with a good sensor point to a refrigerant problem.
- If nothing above is wrong, replace the indoor board.
- After the repair, cycle the power and run the unit to confirm the code does not come back.
Models that show this code
14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit
Other codes on the same units
- P1 Room (intake) air sensor TH1 open or shorted
- P2 Liquid pipe sensor TH2 open or shorted
- P4 Drain float switch disconnected
- P5 Drain overflow - float switch wet with pump running
- P6 Coil freeze or overheat protection
- P8 Pipe temperature out of range (coil not cooling or heating)
- Fb Indoor control board memory error
- PA Water leak detected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-3 Self-diagnosis action table, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.