Mitsubishi · Heat pump
P8 Pipe temperature out of range (coil not cooling or heating)
What the control is telling you
The coil temperature does not move far enough from room temperature: in cooling the coil must be at least 3°C below the return air, in heating at least 3°C above. It takes at least 9 minutes (cooling) or 27 minutes (heating) to detect. Not checked in dry mode or during defrost.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Likely causes
- Low refrigerant charge
- Pipe sensor holder loose on the pipe
- Refrigerant circuit fault
- On multi-unit systems: line sets crossed between units
- On multi-unit systems: indoor/outdoor wires crossed between units
- Room or pipe sensor reading wrong
- Service valves not fully open
Test and repair steps
- Make sure both service valves on the outdoor unit are fully open.
- Check that the TH2 and TH5 sensors are clipped tightly to the pipe.
- Compare room and pipe temperatures on the remote (or with the outdoor A-Control service tool) with real readings.
- Check the refrigerant charge and look for leaks.
- On twin/triple or multiple systems, confirm each line set and S1-S2-S3 wire goes to the matching indoor unit.
- After the repair, cycle the power and run the unit to confirm the code does not come back.
Models that show this code
14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit
Other codes on the same units
- P1 Room (intake) air sensor TH1 open or shorted
- P2 Liquid pipe sensor TH2 open or shorted
- P4 Drain float switch disconnected
- P5 Drain overflow - float switch wet with pump running
- P6 Coil freeze or overheat protection
- P9 Coil sensor TH5 open or shorted
- Fb Indoor control board memory error
- PA Water leak detected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-3 Self-diagnosis action table, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.