Midea · Heat pump
PH90 Evaporator high temperature protection
What the control is telling you
The indoor coil temperature is too high (normally in heating), so the unit protects itself.
Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)
Likely causes
- Low indoor airflow in heating - dirty filter, blower problem, closed registers
- Overcharge
- Indoor coil sensor fault
Test and repair steps
- Check/replace the indoor filter.
- Check indoor blower operation and ductwork/registers.
- Check refrigerant charge.
- Check the indoor coil temperature sensor.
Settings for these units
Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)
| Side | Minimum |
|---|---|
| A - top | 24 in. (610 mm) |
| B - right side (service side) | 24 in. (610 mm) |
| C - front (air outlet) | 24 in. (610 mm) |
| D - left side | 4 in. (101 mm) |
| E - rear (air inlet) | 4 in. (101 mm) |
| Above max snow depth | 2 in. (50 mm) |
Side letters taken from Fig. 8 drawing.
Units facing each other: 59 in. (150 cm) or more; do not blow into another unit's inlet.
Models that show this code
12 models in Midea DLCURA ducted single-zone inverter heat pump (outdoor)
Other codes on the same units
- PC40 Main chip to compressor-driver chip communication error
- PC42 Compressor start failure
- PC43 Compressor lack-phase protection
- PC44 Outdoor unit zero-speed protection
- PC45 Outdoor IR chip drive failure
- PC46 Compressor speed out of control
- PC49 Compressor over-current failure
- PH91 Evaporator low temperature protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.