Lennox · Furnace
E241 Flame sensed out of sequence - flame present
What the control is telling you
Flame is sensed when the gas valve should be closed.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Gas valve leaking through or stuck open
Test and repair steps
- Warning: Shut off gas to the furnace (gas valve switch OFF, by hand only - never use tools; replace the valve if the switch will not move).
- With no call for heat, confirm whether flame is present or flame current is still being sensed.
- Check if the gas valve is being energized without demand (shorted wiring or control relay).
- If the valve leaks through while de-energized, replace it with the same type of valve; do not attempt repair.
- After repair, restore gas, leak-check connections with a gas leak detector (no open flame) and run a full heat cycle.
- Code clears once the fault is gone / flame is proven stable.
Settings for these units
Recommended filter size by cabinet width · EL296UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
Number in brackets is the quantity of filters.
Filters are field supplied and installed outside the furnace; inspect monthly.
Recommended filter size by cabinet width · Lennox SL280UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 14-1/2 in. | 16 x 25 x 1 in. (1) | 14 x 25 x 1 in. (1) |
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
Number in brackets is filter quantity; filters are field supplied.
Never run the unit without a filter installed.
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes by cabinet width · Lennox SL297NV
Models that show this code
34 models in EL296UHV, Lennox SL280UHV, Lennox ML180UHE, Lennox SL297NV
Other codes on the same units
- E227 Low pressure switch opened during ignition or run
- E228 Inducer calibration failure
- E229 Ignition on high fire
- E240 Low flame current (run mode)
- E250 Limit switch circuit open
- E252 Discharge air temperature too high
- E270 Soft lockout - no flame after max retries
- E271 Soft lockout - retries exceeded, pressure switch opened
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Start-Up / Gas Valve Operation p.81. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.