Lennox · Furnace

E241 Flame sensed out of sequence - flame present

Critical severity EL296UHVLennox SL280UHVLennox ML180UHELennox SL297NV

What the control is telling you

Flame is sensed when the gas valve should be closed.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Gas valve leaking through or stuck open

Test and repair steps

  1. Warning: Shut off gas to the furnace (gas valve switch OFF, by hand only - never use tools; replace the valve if the switch will not move).
  2. With no call for heat, confirm whether flame is present or flame current is still being sensed.
  3. Check if the gas valve is being energized without demand (shorted wiring or control relay).
  4. If the valve leaks through while de-energized, replace it with the same type of valve; do not attempt repair.
  5. After repair, restore gas, leak-check connections with a gas leak detector (no open flame) and run a full heat cycle.
  6. Code clears once the fault is gone / flame is proven stable.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

34 models in EL296UHV, Lennox SL280UHV, Lennox ML180UHE, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DKSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • E227 Low pressure switch opened during ignition or run
  • E228 Inducer calibration failure
  • E229 Ignition on high fire
  • E240 Low flame current (run mode)
  • E250 Limit switch circuit open
  • E252 Discharge air temperature too high
  • E270 Soft lockout - no flame after max retries
  • E271 Soft lockout - retries exceeded, pressure switch opened

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Start-Up / Gas Valve Operation p.81. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.