Lennox · Furnace

E229 Ignition on high fire

Low severity EL296UHVLennox SL280UHVLennox SL297NV

What the control is telling you

Control switched to high-fire ignition because the low-fire pressure switch did not close in time. Informational.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Low supply voltage
  • Low outdoor temperature
  • Marginal low-fire pressure differential

Test and repair steps

  1. No repair is required for this code by itself.
  2. Sequence if the low-fire switch does not close, the inducer goes to high, the high-fire switch closes after the 15 s pre-purge and the furnace lights on high fire, switching to low fire after 10-20 seconds.
  3. If it repeats often, check line voltage (97-132 VAC hot to neutral) and supply voltage under load.
  4. Check the vent system and condensate drainage, and measure low-fire pressure switch differential against the set-point tables.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

22 models in EL296UHV, Lennox SL280UHV, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • E225 High pressure switch failed open
  • E226 High pressure switch failed closed
  • E227 Low pressure switch opened during ignition or run
  • E228 Inducer calibration failure
  • E240 Low flame current (run mode)
  • E241 Flame sensed out of sequence - flame present
  • E250 Limit switch circuit open
  • E252 Discharge air temperature too high

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Wiring and Sequence of Operation p.93. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.