Lennox · Furnace

E201 Indoor blower communication failure

High severity EL296UHVLennox SL280UHVLennox SL297NV

What the control is telling you

The control lost communication with the indoor blower motor, including a motor power loss.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Motor not powered
  • Loose motor wiring
  • Fault on control or motor side

Test and repair steps

  1. Warning: Disconnect power before checking motor connections.
  2. Check line power to the blower motor.
  3. Check the motor harness and communication connections at both ends.
  4. Determine whether the fault is on the control or motor; replace the failed part.
  5. Clears after the fault recovers.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

22 models in EL296UHV, Lennox SL280UHV, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • E180 Outdoor air temperature sensor failure
  • E200 Flame rollout - hard lockout
  • E202 Blower motor mismatch
  • E203 Unit capacity not programmed
  • E204 Gas valve miswired
  • E205 Gas valve relay contact shorted
  • E206 Gas valve second-stage relay failure
  • E207 Hot surface ignitor open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.34; Ignition Control 107045-XX Diagnostic Codes table, p.41. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.