Lennox · Furnace

4 flashes Low flame signal

Medium severity Lennox EL195UHNE

What the control is telling you

Flame signal is weak. The control keeps running but warns that the flame sensor needs attention.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • Oxidized or dirty flame sensor
  • Sensor bent away from flame
  • Poor ground
  • Incorrect combustion (manifold/air orifice)

Test and repair steps

  1. Use the recall button / meter to read flame current. Read flame signal: normal 2.6 uA or more, low 2.5 uA or less, drop-out 1.1 uA (Table 7). Note: the troubleshooting flowchart uses 1.5 uA as the low limit.
  2. Warning: Shut off power and gas before removing the sensor (top of the air gas plenum).
  3. Clean the sensor rod and check its position; replace if damaged.
  4. Check the burner ground and Check ground at the control: AC volts between line neutral and the C terminal should be about 0.3 V (2 V max) at idle, 0.75 V (5 V max) with inducer/ignitor on, under 2 V (10 V max) with blower on; line hot to neutral should be 97-132 VAC.
  5. Check manifold pressure and the air orifice size if the flame is poor.

Settings for these units

Filter sizes (filter rack kits) · Lennox EL195UHNE

CabinetHorizontal end rackSide return rack
B width (040, 060)18 x 25 x 1 (kit 87L96)16 x 25 x 1 (kit 44J22)
C width (080, 100)20 x 25 x 1 (kit 87L97)16 x 25 x 1 (kit 44J22)

Filters are field supplied; check monthly.

100NE60C over 1800 cfm with single side return needs a 20 x 25 x 1 filter via return air base and transition.

Models that show this code

4 models in Lennox EL195UHNE

EL195UH040NE36BEL195UH060NE36BEL195UH080NE48CEL195UH100NE60C

Other codes on the same units

  • 1 flash Line voltage polarity reversed
  • 2 flashes Improper earth ground
  • 3 flashes Burner failed to light or lost flame
  • 5 flashes Watchguard - ignition retries/recycles exceeded
  • 7 flashes Primary or secondary limit open
  • 8 flashes Rollout switch open
  • 9 flashes Pressure switch stays open or drops out on a heat call
  • 10 flashes Watchguard - pressure switch opened 5 times in one heat demand

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; Table 7, p.12. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.