Lennox · Furnace
3 flashes Burner failed to light or lost flame
What the control is telling you
The burner did not light, or flame was lost during the heat call.
Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)
Likely causes
- Gas off or low supply pressure
- Ignitor not glowing
- Dirty or poorly placed flame sensor
- Wrong air orifice (hard ignition)
- Poor ground
- Restricted vent/intake or plugged condensate drain
Test and repair steps
- Confirm gas is on at the meter and both manual shut-off valves are open; supply 4.5-10.5 in. w.c. natural gas.
- Watch a cycle 15 s pre-purge, 20 s ignitor warm-up, gas valve opens for a 4 s trial; control retries four more times.
- Check ignitor 39-70 ohms across plug terminals 1 and 5; voltage 120 V +/-10% during warm-up.
- Read flame signal normal 2.6 uA or more, low 2.5 uA or less, drop-out 1.1 uA (Table 7). Note: the troubleshooting flowchart uses 1.5 uA as the low limit. Clean or replace the sensor if low.
- Check manifold pressure 3.2-3.8 in. w.c. (0-4500 ft, natural gas) and signal pressure per Table 19.
- If ignition is rough or delayed, check the air orifice part number against Table 20 and follow the poor ignition/resonance guide.
- Check ground and polarity at the control.
Settings for these units
Filter sizes (filter rack kits) · Lennox EL195UHNE
| Cabinet | Horizontal end rack | Side return rack |
|---|---|---|
| B width (040, 060) | 18 x 25 x 1 (kit 87L96) | 16 x 25 x 1 (kit 44J22) |
| C width (080, 100) | 20 x 25 x 1 (kit 87L97) | 16 x 25 x 1 (kit 44J22) |
Filters are field supplied; check monthly.
100NE60C over 1800 cfm with single side return needs a 20 x 25 x 1 filter via return air base and transition.
Models that show this code
4 models in Lennox EL195UHNE
Other codes on the same units
- 1 flash Line voltage polarity reversed
- 2 flashes Improper earth ground
- 4 flashes Low flame signal
- 5 flashes Watchguard - ignition retries/recycles exceeded
- 7 flashes Primary or secondary limit open
- 8 flashes Rollout switch open
- 9 flashes Pressure switch stays open or drops out on a heat call
- 10 flashes Watchguard - pressure switch opened 5 times in one heat demand
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; p.12-13, 40-45. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.