KeepRite · Air conditioner
71 Low stage thermal cutout
What the control is telling you
Compressor ran on low stage, then disappeared while low-stage demand remained.
Applies to: KeepRite *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating
Likely causes
- Compressor internal overload trip
- Start relay/capacitor left in circuit too long
Test and repair steps
- Check voltage and contactor.
- Check windings once cool (see two-stage resistance table).
- Check start components if fitted.
Settings for these units
- Outdoor unit clearances · KeepRite C4A3/CXA6 AC
Models that show this code
8 models in KeepRite *CA/*CH Two-Stage Communicating
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.