KeepRite · Air conditioner

71 Low stage thermal cutout

High severity KeepRite *CA/*CH Two-Stage Communicating

What the control is telling you

Compressor ran on low stage, then disappeared while low-stage demand remained.

Applies to: KeepRite *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating

Likely causes

  • Compressor internal overload trip
  • Start relay/capacitor left in circuit too long

Test and repair steps

  1. Check voltage and contactor.
  2. Check windings once cool (see two-stage resistance table).
  3. Check start components if fitted.

Settings for these units

Models that show this code

8 models in KeepRite *CA/*CH Two-Stage Communicating

*CA624*CA636*CA648*CA660*CA924*CA936*CA948*CA960

Other codes on the same units

  • 47 No 230 V at the unit
  • 53 Outdoor air temperature sensor fault
  • 55 Outdoor coil sensor fault
  • 56 Air and coil sensors disagree
  • 72 Compressor thermal cutout (two-stage: high stage)
  • 73 Contactor stuck closed
  • 74 No 230 V at compressor
  • 81 Low stage thermal lockout

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.