Gree · Heat pump

P8 Inverter module overheated

High severity Gree SapphireGree Livo GEN4Gree Vireo GEN3Gree Multi21+Gree GMV6 Mini VRF

What the control is telling you

The compressor drive module (IPM) got too hot, so the compressor stops.

Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO), GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

Likely causes

  • Dried or missing thermal paste under the IPM
  • Heat sink screws loose
  • Poor outdoor airflow or very high load
  • Board fault

Test and repair steps

  1. Warning: Kill power and let the outdoor board capacitors bleed down (about 20 min, or meter the DC bus below 20 V) before touching the inverter board.
  2. Check thermal paste between the IPM and heat sink and that the heat sink is tightly screwed down.
  3. Clean the outdoor coil and check the outdoor fan.
  4. If the code continues, replace the outdoor board.

Models that show this code

17 models in Gree Sapphire, Gree Livo GEN4, Gree Vireo GEN3, Gree Multi21+, Gree GMV6 Mini VRF

3VIR09HP115V1A3VIR09HP230V1A3VIR12HP115V1A3VIR12HP230V1A3VIR18HP230V1A3VIR24HP230V1A4LIV30HP230V1AH4LIV36HP230V1AHGMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)MULTI18HP230V1COMULTI24HP230V1COSAP09HP230V1AHSAP12HP230V1AHSAP18HP230V1AHSAP24HP230V1AH

Other codes on the same units

  • P4 Compressor drive PFC protection
  • P5 Compressor phase overcurrent
  • P6 Compressor drive IPM protection
  • P7 Inverter module temperature sensor fault
  • P9 Inverter compressor lost synchronism
  • U0 Compressor preheat not finished
  • U1 Compressor phase current sensing fault
  • U2 Outdoor capacity code / jumper wrong

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination; Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.