Goodman · Heat pump

03 Short cycling

Medium severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

Each of the last 4 run cycles lasted under 3 minutes, with no protector trip and both pressure switches closed. While this code is active the minimum compressor run time is raised from 30 seconds to 3 minutes.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Thermostat call dropping in and out (loose wire, bad thermostat, poor location)
  • Faulty compressor relay on the outdoor control

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Check the thermostat and its wiring for loose or intermittent connections; repair or replace.
  3. Check the compressor relay on the control; replace the control if it misbehaves.
  4. Clears after 4 normal cycles in a row, or by power cycling the 24 VAC.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

  • 01 Low side fault or low pressure switch trip
  • 02 High side fault or high pressure switch trip
  • 04 Locked rotor
  • 05 Open circuit - compressor off over 4 hours
  • 06 Open start circuit
  • 07 Open run circuit
  • 08 No line voltage
  • 09 Low 24 V control voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.