Goodman · Heat pump
09 Low 24 V control voltage
What the control is telling you
The control sees its 24 V supply below 18 VAC. The unit may still seem to run. Clears when the control voltage goes back above 21 VAC.
Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18
Likely causes
- Overloaded transformer
- Low line voltage
- Fuse or wiring problem in the 24 V circuit
Test and repair steps
- Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
- Check the low voltage fuse.
- Measure 24 V at the control (R to C) with all loads on; reduce load or replace the transformer if it sags.
- Check line voltage feeding the transformer.
Models that show this code
24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.