Goodman · Air conditioner

CoreSense solid red Solid red TRIP - call present but compressor not running

High severity Goodman/Amana R-32 GLXS/ALXSGoodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

What the control is telling you

Red LED steady: the module sees a Y demand but the compressor is not running.

Applies to: Copeland CoreSense 3-wire module: Amana/Deluxe R-410A ASX, ASZ, DSX, DSZ units and Amana R-32 ALXS / ALZS units

Likely causes

  • Compressor protector open (check head pressure and compressor voltage)
  • Outdoor disconnect open
  • Compressor breaker or fuses open
  • Broken wire or poor connector
  • High pressure switch open (if fitted)
  • Contactor failed open

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Check disconnect, breaker and fuses.
  3. Check contactor coil voltage and contacts.
  4. Check head pressure and compressor supply voltage; let a hot compressor cool.
  5. Check the high pressure switch and wiring.

Models that show this code

150 models in Goodman/Amana R-32 GLXS/ALXS, Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

ALXS3BN**10AAALXS4BA**10AAALXS4NA**10AAALXS5BA**10AAANX130181ANX130241ANX130301ANX130361ANX130421ANX130481ANX130601ANX130611ANX140181ANX140191ANX140241ANX140251ANX140301ANX140361ANX140371ANX140421ANX140431ANX140481ANX140601ASX130181ASX130241ASX130301ASX130361ASX130421ASX130481ASX130601ASX130611ASX140181ASX140191ASX140241ASX140251ASX140301ASX140311ASX140361ASX140371ASX140421ASX140431ASX140481ASX140601ASX160181ASX160241ASX160301ASX160311ASX160361ASX160371ASX160421ASX160481ASX160601ASX160611ASX180**1ABASXH5***10DSX160241DSX160361GLXS3BN**10AAGLXS4BA**10AAGLXS4MA**10AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), CoreSense Diagnostics Table p.21-22 and Quick Reference Table p.23; Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) (Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt section Diagnostics Table: Coresense Module / Table 1 Quick Reference). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.