Goodman · Air conditioner
CoreSense 1 Yellow 1 flash - long run time (low side)
What the control is telling you
Compressor has run more than 18 hours straight, showing low capacity from a low-side problem. This code is disabled in heat pump heating mode.
Applies to: Copeland CoreSense 3-wire module: Amana/Deluxe R-410A ASX, ASZ, DSX, DSZ units and Amana R-32 ALXS / ALZS units
Likely causes
- Low charge
- Indoor blower not running (relay, capacitor, motor, wiring, indoor board, open thermostat wire)
- Frozen evaporator (low suction, low set point, blocked coil/filter/ducts)
- Metering device stuck or TXV bulb badly mounted
- Restricted liquid line drier
- Thermostat short or poor location
Test and repair steps
- Check charge and look for leaks.
- Verify the indoor blower and its control; clean filter and coil, open registers.
- Check TXV bulb size, location and contact; check for a stuck TXV or piston.
- Check the drier for a temperature drop.
- Check thermostat sub-base, wiring and location.
Models that show this code
150 models in Goodman/Amana R-32 GLXS/ALXS, Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)
Other codes on the same units
- Comfort Alert 7 Yellow ALERT 7 flashes - open run circuit
- Comfort Alert 9 Yellow ALERT 9 flashes - low control voltage
- Comfort Alert TRIP Red TRIP LED - call present but compressor not running
- Comfort Alert TRIP+ALERT TRIP and ALERT LEDs flashing together - control voltage too low
- CoreSense 2 Pressure trip - yellow 2 flashes (red 2 = lockout)
- CoreSense 3 Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
- CoreSense 4 Locked rotor - yellow 4 (red 4 = lockout)
- CoreSense 5 Moderate run trip - yellow 5 (red 5 = lockout)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), CoreSense Diagnostics Table p.21-22 and Quick Reference Table p.23; Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) (Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt section Diagnostics Table: Coresense Module / Table 1 Quick Reference). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.