Goodman · Air conditioner

b0 Indoor blower not running when it should be

High severity Goodman/Amana ComfortNet ASXC/GSXC/DSXC

What the control is telling you

The outdoor unit sees that the indoor circulator blower is off during a call that needs airflow, so the outdoor unit will not run.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Indoor blower motor or motor wiring problem
  • Communication error between the indoor and outdoor units
  • Indoor control fault

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Read the indoor unit's 7-segment display for its own code (for example Eb0-Eb9) and follow that code first.
  3. Check the blower motor power and 4-wire communication harness between the indoor control and the motor.
  4. Verify the indoor control is working and talking on the network; repair any wiring faults.
  5. Repair or replace the indoor blower motor or indoor control as found.

Models that show this code

23 models in Goodman/Amana ComfortNet ASXC/GSXC/DSXC

ASXC160241ASXC160361ASXC160481ASXC160601ASXC180241ASXC180361ASXC180481ASXC180601DSXC160241DSXC160361DSXC160481DSXC160601DSXC180361DSXC180481DSXC180601GSXC160241GSXC160361GSXC160481GSXC160601GSXC180241GSXC180361GSXC180481GSXC180601

Other codes on the same units

  • 06 Open start circuit
  • 07 Open run circuit
  • 08 No line voltage
  • 09 Low 24 V control voltage
  • b9 Indoor airflow lower than requested
  • d0 No shared data on the network
  • d1 Invalid shared data on the network
  • d2 System mismatch - indoor unit cannot supply required airflow

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.