Fujitsu · Heat pump

53 Drain pump error

Medium severity Fujitsu ductless split/multi/VRF (general code list)Fujitsu wall-mounted 7-15 (NA ASU/AOU type)Fujitsu slim duct ARU 7-18 (LL type)

What the control is telling you

Condensate is not being removed by the drain pump (float stays high). Indoor lamps: OPERATION (green) flashes 5x, TIMER (orange) flashes 3x, ECONOMY (green) flashes fast nonstop; wired remote shows 53.

Applies to: Fujitsu ductless heat pumps: Fujitsu ductless split/multi/VRF (general code list), Fujitsu wall-mounted 7-15 (NA ASU/AOU type), Fujitsu slim duct ARU 7-18 (LL type)

Likely causes

  • Blocked drain line or pan
  • Drain pump failed
  • Float switch fault

Test and repair steps

  1. Warning: Check for water overflow before resetting.
  2. Clear the drain pan and line.
  3. Test pump and float switch; replace the failed part.
  4. On ducted units without a pump, DIP SW101-1 must be set to disable the drain function.

Settings for these units

Other codes on the same units

  • 42 Indoor coil (heat exchanger middle) sensor error
  • 44 Human (occupancy) sensor error
  • 51 Indoor fan motor error
  • 52 Indoor electronic expansion valve error
  • 57 Damper error
  • 58 Intake grille error
  • 61 Outdoor reverse / missing phase or wiring error
  • 62 Outdoor main PCB error (EEPROM / model / micro comms)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu All Fujitsu split - multi - VRF (generic code list) codes.pdf - section error code table (indoor LED flashes); Fujitsu Wall-mounted 7-9-12-15 (North American trilingual, UTY-RNNUM remotes; e.g. ASU9-12-15 RLF1-RLS familie.pdf - section 14 Error codes; Fujitsu Slim duct AR07-09-12-14-18 (ARU-ARYG LL-type equivalent) installation P-N 9381858064.pdf - section 14 Error codes. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.