Daikin · Furnace

EEA Reversed line polarity or grounding error

High severity Daikin DR96TN/DD96TN

What the control is telling you

The control detected that the 115 VAC hot and neutral are reversed, or the unit ground is poor. The furnace will not operate.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Hot and neutral swapped at the furnace or panel
  • Poor or missing ground wire
  • Transformer primary/secondary out of phase

Test and repair steps

  1. Warning: line voltage present - use care when measuring.
  2. Check that the black (hot) and white (neutral) supply wires land on the correct terminals; correct the polarity.
  3. Confirm there is a ground wire from the furnace j-box right back to the panel. Gas pipe or conduit does not count as ground.
  4. Power off and measure resistance from the neutral (white) connection to the burner nearest the flame sensor - it should be very low (the manuals give less than 2 ohms and also 10 ohms or less).
  5. If an unmarked transformer was replaced, check phasing: about 96 VAC between the connected primary/secondary leads means in phase, about 144 VAC means out of phase - reverse the low voltage leads.

Settings for these units

Normal status displays (7-segment) · Daikin DR96TN/DD96TN

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat, low stagegH1
Gas heat, high stagegH2
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Models that show this code

13 models in Daikin DR96TN/DD96TN

DD96TN0403BNDD96TN0603BNDD96TN0803BNDD96TN1005CNDR96TN0303ANDR96TN0403ANDR96TN0603ANDR96TN0603BNDR96TN0803BNDR96TN0804CNDR96TN1004CNDR96TN1005CNDR96TN1205DN

Other codes on the same units

  • EAF R-32 sensor communication lost - mitigation mode
  • EAL R-32 refrigerant leak detected - mitigation mode
  • EAS R-32 sensor fault - mitigation mode
  • EAr A2L relay fault - mitigation mode
  • EEC Internal gas valve error - valve energized when it should not be
  • EEE Internal control fault (IRQ loss)
  • EEH Twinning error
  • EEJ Inducer relay error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Servicing - polarity and phasing p.15. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.