Carrier · Furnace

34.3 Flame lost after blower on-delay

High severity 59SC6A

What the control is telling you

Flame was proven after ignition but then lost after the heating blower on-delay, with the blower running.

Applies to: Carrier 59SC6A

Likely causes

  • Blower airflow disturbing the flame (cabinet/heat exchanger leakage)
  • Dirty flame sensor
  • Gas pressure drop
  • Vent issue
  • Return air drawn from the furnace space

Test and repair steps

  1. Warning: Flame disturbed when the blower starts can point to a heat exchanger or cabinet leak; inspect carefully before returning the unit to service.
  2. Confirm the blower door is installed and return duct is sealed to the furnace.
  3. Clean the flame sensor with 0000 steel wool only.
  4. Check gas pressure with the blower running.
  5. Inspect vent and combustion-air pipes.
  6. Inspect heat exchanger cells; clean openings with vacuum and soft brush if burner assembly is removed.
  7. Run 2 complete cycles watching for flame lift or roll when the blower starts (25 s after the gas valve opens).

Settings for these units

Filter sizes by casing width and filter cabinet · 59SC6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide(1) 16 x 25 x 3/4 in.(1) 20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media

Side-return filters can differ in size - measure the existing filter.

Every return-air inlet needs a filter.

Minimum clearances to combustibles · 59SC6A

PositionMinimum clearance
Rear0
Front (combustion air openings in furnace and in structure)1 in. (25 mm)
Required for service24 in. (610 mm) (see note)
All sides of supply plenum1 in. (25 mm) (see note)
Sides0
Vent0
Top of furnace1 in. (25 mm)

Service and supply-plenum values are marked 'consult local building codes'.

Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.

Models that show this code

11 models in 59SC6A

59SC6A026M14--1059SC6A040M14--1059SC6A040M17--1259SC6A060M14--1259SC6A060M17--1659SC6A080M17--1659SC6A080M21--2059SC6A100M21--2059SC6A100M21--2259SC6A120M24--2259SC6A140M24--22

Other codes on the same units

  • 32.1 Main pressure switch (LPS) open
  • 33.1 Main limit circuit switch open
  • 34.1 Ignition fault during ignition trials
  • 34.2 Flame lost before blower on-delay
  • 45.1 Control failure - flame circuit / memory / sequence
  • 45.2 Control failure - gas valve relay will not close
  • 45.3 Control failure - EEPROM memory
  • 46.1 Momentary loss of power

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; Sequence of Operation p.69; Heat exchanger cleaning p.68. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.