Carrier · Furnace
33 Limit circuit fault
What the control is telling you
The limit or a flame rollout switch is open, or the furnace is in high-heat-only mode after 2 successive low-heat limit trips. Blower runs at least 4 minutes; if open over 3 minutes the code becomes lockout 13.
Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)
Likely causes
- Loose blower wheel
- Defective switch or connections
- Improper low- or high-heat gas input
- Wrong limit switch or no limit gasket
- Dirty filter or restricted ducts
- Open flame rollout switch (manual reset)
Test and repair steps
- Warning: Shut off 115-V power and gas, and lock/tag out before working inside the furnace; there may be more than one power source.
- Replace dirty filters and check supply/return ducts for restrictions.
- Check the blower wheel is secure.
- Check gas input by clocking the meter and manifold pressure in both stages.
- Inspect the limit switch, its gasket and wiring; replace if defective or incorrect.
- If the rollout switch is open, correct combustion air, gas pressure, burner/orifice alignment or venting before manually resetting it.
- Verify temperature rise is within the rating-plate range after repair.
Settings for these units
Filter sizes by casing width and filter cabinet · 59TP6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | 16 x 25 x 3/4 in. | 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | 16 x 25 x 3/4 in. | 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | 16 x 25 x 3/4 in. | 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
No internal filter rack in this furnace - an external filter is required.
Side-return filters can differ in size - measure the existing filter.
Minimum clearances to combustibles · 59TP6A
| Position | Clearance |
|---|---|
| Rear | 0 in. (0 mm) |
| Front (combustion air openings) | 1 in. (25 mm) |
| Front, required for service | 24 in. (610 mm) - check local code |
| All sides of supply plenum | 1 in. (25 mm) - check local code |
| Sides | 0 in. (0 mm) |
| Vent | 0 in. (0 mm) |
| Top of furnace | 1 in. (25 mm) |
Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.
Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.
- Filter sizes by casing width · 58SB0A/58SB1A
Models that show this code
22 models in 59TP6A, 58SB0A/58SB1A
Other codes on the same units
- 25 Invalid model selection or setup error
- 31 High-heat pressure switch or relay did not close or reopened
- 32 Low-heat pressure switch did not close or reopened
- 34 Ignition proving failure
- 43 Low-heat pressure switch open while high-heat switch closed
- 45 Control circuitry lockout
- LED OFF No amber LED - no power to control
- Rapid Flash Reversed 115-V polarity (or twinning phasing)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide (cont.), p.89. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.