Bosch · Heat pump
E52 DC bus voltage out of range
What the control is telling you
The DC bus voltage on the outdoor unit is too high or too low.
Applies to: Bosch IDS Light BOVA15-24/36/60 and IDS Premium Connected BOVA36-20/60-20 R-454B heat pump outdoor units
Likely causes
- Supply voltage out of range (aim for 187-253 VAC)
- Wrong input wiring
- Shorted compressor or fan motor
- Control board fault
Test and repair steps
- Warning: Switch off power and wait 3 minutes before measuring resistance or touching boards.
- Verify supply wiring and voltage between 187 and 253 VAC.
- Check compressor windings U/V/W (under 1 ohm between phases, over 1 Mohm to ground).
- Check fan motor windings and replace motor or compressor if failed.
- Replace the outdoor control board if the fault shows in standby.
Models that show this code
5 models in Bosch IDS Light, Bosch IDS Premium Connected
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch IDS Light installation BTC 762003308 D (02.2025), Fault Code Table 23 and 17.12 Error Code Troubleshooting, p.42-59; Bosch IDS Premium Connected installation BTC 762003301 D (02.2025), Fault Code Table 22 and 18.12 Error Code Troubleshooting. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.