Midea · technician tips
Midea service menus, test modes and resets
4 tips for furnace, mini split: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Service & test modes (2) · Reset & cancel (1) · Other (1)
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Read live data with the outdoor check button (SW1)
Mini split · Midea DLCM(R/H)B multi-zone outdoor
Each press of SW1 steps through a value on the outdoor display.
- Press 1 = number of indoor units talking. 2 = mode (0 off, 1 fan, 2 cool, 3 heat, 4 forced cool, A forced defrost).
- Presses 17-21 = T2B per zone, 22-26 = room temp per zone, 27-31 = coil temp per zone, 32 = T3, 33 = T4, 34 = discharge temp.
- Press 45 (all sizes) = last fault or protection (00 = none). See the check switch table for the full list; the 18K board uses a slightly different order.
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Tables 25-26 p.29-31. Written in our own words; check the manual for your exact model.
Run the automatic wiring / piping correction
Mini split · Midea DLCM(R/H)B multi-zone outdoor
The outdoor unit can find and fix crossed wiring vs piping ports by itself.
- Outdoor temperature must be above 41 F (5 C). Indoor units do not need to be running.
- Hold CHECK (SW1) on the outdoor board about 6 seconds until CE shows (FA may show first, keep holding).
- Indoor units go to 76 and the compressor runs for about 5-10 minutes.
- When CE changes to 00 it is done. Set each indoor unit back with its remote (they stay at 76).
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Automatic Wiring/Piping Correction p.6. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Clear an ignition lockout (E7) early
Furnace · Midea 96% AFUE A2L Gas Furnace (BGH96M)
After two failed ignition attempts the control locks out with E7.
- Remove 115 V power or the thermostat call for 1-20 s.
Applies to: BGH96M060B3A, BGH96M080B3A, BGH96M080C4A, BGH96M100C5A, BGH96M100D5A, BGH96M120D5A
Source: Midea A2L 96% AFUE Gas Furnace Troubleshooting Guide, Appendix A Sequence of Operation, Figures 24-26, p.7, 11, 24-26. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Discharge the inverter capacitors before service
Mini split · Midea DLCM(R/H)B multi-zone outdoor, Midea DLFSHBH wall indoor (DLCM multi-zone)
The big electrolytic capacitors on the outdoor board stay charged after power-off.
- Turn power off and lock out.
- Put a resistor of about 100 ohm 40 W (or a soldering iron plug) across the + and - capacitor terminals before touching the board.
Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)
Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Troubleshooting Safety p.16. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.