3 double red flashes Second-stage pressure switch not closing
What the control is telling you
Two-stage boards (UTEC / White-Rodgers): the high-fire pressure switch stays open on a second-stage call. TM9V boards report this as 13 red flashes instead.
Applies to: York/JCI residential gas furnaces: York UTEC IFC furnaces, York White-Rodgers IFC furnaces
Likely causes
- Partly blocked vent or intake
- Inducer not reaching high speed
- Hose or wiring problem at the high-fire switch
- Faulty high-fire switch
Test and repair steps
- Check vent/intake for partial restriction.
- Confirm the inducer reaches high speed on a W2 call.
- Check the high-fire switch hose and wires.
- Test and replace the switch if it does not close.
- To read stored codes with no thermostat call active, tap the LAST ERROR button briefly (under 5 s); up to five codes play back newest first. Two green flashes = memory empty. Hold the button 5 s or more to clear (three green flashes confirm).
Settings for these units
- Clearance to combustibles · York TM9V
- Filter size by return location · York TM9V
Other codes on the same units
- 1 red flash Flame detected with gas valve off
- 2 red flashes Pressure switch closed when it should be open
- 3 amber flashes W2 call without W1
- 3 red flashes Pressure switch open when it should be closed
- 4 amber flashes Cooling call (Y) without fan call (G)
- 4 red flashes Main limit switch open
- 5 red flashes Rollout switch open / limit circuit open over 15 min
- 6 red flashes Pressure switch cycling lockout
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: York All JCI single-two-stage furnaces with UTEC IFC board codes ST-045-09.pdf - section Fault Code LED Flashes; York JCI single-two-stage furnaces with White-Rodgers-Emerson IFC (older installed base) codes ST-028-07.pdf - section Fault Code Sheets. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.